2 HP, 460 V
Unit of Measure

Specifications

Voltage

N/A 460 V

Phase

N/A Three

Frequency

N/A 50/60 Hz

HP Rating

N/A 2

kW Rating

N/A 1.5

Rated Output Amps

N/A 4.1

Overload Amps (110% 1 Min)

N/A 4.5

Standard Unit Includes

N/A IP20 (9) Chassis RFI: A2 Keypad

Factory Installed Keypad

N/A Keypad

Drive Type

N/A IP20/Open

A1/B RFI Filter

N/A No A1/B RFI Filter Installed

Load Share

N/A Standard Unit

Conformal Coating

N/A No Conformal Coatings

Revision

N/A 1st Revision

Option Kits

N/A , Field Installed IP21/NEMA 1 Add-On Option Kits for AF-650 GP General Purpose Drive ($110.00)

Options and Accessories

N/A , 24V DC External Supply Module ($240.00)
, Pedestal Kit ($875.00)
, Analog I/O Module ($500.00)
, BacNet Communications Module ($600.00)
, Power Shield for Unit Size 41 and 42 Drive ($520.00)
, Power Shield for Unit Size 51 Drive ($1,305.00)
, DeviceNet Communications Module ($600.00)
, Ethernet IP Communications Module ($700.00)
, General Purpose I/O Module ($475.00)
, LonWorks Communications Module ($600.00)
, Modbus TCP Communications Module ($700.00)
, Profibus DP Communications Module ($725.00)
, ProfiNet RT Communications Module ($700.00)
, Relay Output Module ($475.00)
, Remote Mounting Kit without cable ($85.00)
, Screw Terminal Accessory ($25.00)
, USB Kit for All Drives up to Unit Size 5X ($75.00)
, USB Kit for All Unit Size 6X drive ($225.00)
, Remote Mounting Kit for Graphical LCD Keypad ($95.00)

Environmental Conditions

Enclosure

N/A IP00 Chassis IP20 Chassis IP21/NEMA 1 IP54/NEMA 12 IP55/NEMA 12

Plenum Ratings

N/A Drives and options are UL rated for installation inside air handling ducts and plenums

Installation Location

N/A Do not install in locations where product could be exposed to dust, corrosive gas, inflammable gas, oil mist, vapor, water drops or direct sunlight. There must be no salt in the atmosphere. Condensation must not be caused by sudden changes in temperature. For use at altitudes of 3280 ft. (1000 M) or less without derating.

Storage Temperature

N/A -25 to 65 ºC
Ambient Temperature1 N/A -10 to +50 ºC

Ambient Humidity

N/A 5 to 95 % RH (non-condensing)

Vibration

N/A 1.0 g

Cooling Method

N/A Fan Cooled all ratings. Fan Control Auto, 50% level, 75% level, 100% level adjustable

Standards

Approvals

N/A CE, UL, cUL, and C-Tick
Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes for 208/230 V and 460 V.

Input Power Supply

Rated Input AC Voltage

N/A 200-240 Vac, 3-phase, 50-60 Hz, ± 10 % V 380-480 Vac, 3-phase, 50-60 Hz, ± 10 % V 525-600 Vac, 3-phase, 50-60 Hz, ± 10 % V

Max. Voltage Imbalance

N/A 3 % of rated supply voltage

True Power Factor

N/A > 0.9 nominal at rated load

Displacement Power Factor

N/A > 0.98

Switching on Input Power Supply

N/A Maximum twice/minute up to 10 HP, Maximum once/minute above 10 HP

Environment According to EN60664-1

N/A Overvoltage category III/pollution degree 2

DC Link Reactors

N/A Built-In DC Link Reactors on all ratings

RFI Filters

N/A Built-In RFI Filters to reduce noise generated by the drive. Meets industrial standards.

Output

Rated Output Voltage

N/A 0-100 % of supply voltage

Output Frequency

N/A 0-1000 Hz; 0-800 Hz for 460 V above 125 HP and 525-690 V above 125 HP

Switching on Output

N/A Unlimited

Accel/Decel Times

N/A 1 to 3600 s

Control Method

N/A Sinusoidal PWM Control (V/Hz, Avd. Vector Control)

Control

Starting Torque

N/A 110 % starting torque for 1 minute (variable torque)

Carrier Frequency (Motor Noise)

N/A 1 kHz1.5 kHz2 kHz2.5 kHz3 kHz3.5 kHz4 kHz5 kHz6 kHz7 kHz8 kHz10 kHz12 kHz14 kHz16 kHz

Torque Boost

N/A 0-300 % setting to compensate voltage in relation to the load at low speed

Acceleration/Deceleration Time

N/A 0.01-3600 seconds (4 acceleration and deceleration times are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or S-curve)

Data Protection

N/A Password Protection for Quick Menu or Main Menu, 0-9999.

Pattern Operation

N/A Settings via Built-In Logic Controller Sequencer

Jump Frequency Control

N/A 4 jump (or skip) frequencies via parameter set to avoid mechanical vibration

Slip Compensation

N/A Maintains motor at constant speed with load fluctuations

Torque Limit Control

N/A Output torque can be controlled within a range of 0.0 to 110 % (0.1 and steps)

8 Preset Speeds

N/A 8 programmable preset speeds selectable by 3 digital inputs

Preset Speeds

N/A 8 presets via digital inputs

Built-In Communications

N/A Drive RS-485, Modbus RTU, Metasys N2, or Apogee FLN P1

Trim Reference Setting

N/A Available for speed reference offset via potentiometer, voltage input, or current input

DC Injection Braking

N/A Starting frequency: 0.0-1000 Hz, 0-800 Hz for 460 V above 125 HP and 525-690 V above 125 HP
Braking time: 0.0-60.0 seconds
Braking level: 0-100 % of rated current

Jogging Operation

N/A Operation via On key or digital input (Fwd or Rev)

Auto-Restart After Power Failure

N/A Restarts the drive without stopping after instantaneous power failure

Energy Savings

N/A Controls output voltage to minimize motor loss during constant speed operation

Start Mode Function

N/A This functionality smoothly catches a spinning motor

Fire Override Mode

N/A Overrides drive's protective features and keeps motor running

Pump Cascade Controller

N/A Distributes running hours evenly over up to 4 pumps

Sleep Mode

N/A Drive detects low or no flow conditions and adjusts output

Dry Pump Detection

N/A Detects pump operation and can set off alarm, shuts off, or other programmed actions

Belt Monitoring

N/A Drive can detect relationship between current and speed to recognize a broken belt

Real Time Clock

N/A With programmable timed actions

Logic Controller (LC) Sequencer

Logic Controller Events

N/A Up to 38 Programmable Events

Comparators

N/A Array of 6 Comparators

Timers

N/A Array of 8 Timers, adjustable from 0.0 to 3600 sec

Logic Rules

N/A Array of 6 Boolean Logic Rules

Logic Controller States

N/A Array of 20 Logic Controller Action States

Process Controller (PID)

Process PID Controller

N/A 4 Auto Tune PID Controllers Built-In
Process CL Feedback Select2 N/A Encoder Option Module Motor Feedback No function Resolver Option Module Separate Encoder

Process PID Control

N/A Inverse Normal

Process PID Anti Windup

N/A Disabled Enabled

Process PID Start Speed

N/A 0.0 to 200 Hz

Process PID Proportional Gain

N/A 0.00 to 10.00

Process PID Integral Time

N/A 0.1 to 10000.0 ms

Process PID Differential Time

N/A 0.0 to 10 s

Process PID Differential Gain

N/A 1.0 to 50.00

Process PID Feed Forward Factor

N/A 0 to 500 %

On Reference Bandwidth

N/A 0 to 200 %

Operation

Operation Method

N/A Keypad operation: Hand, Off, Auto
Digital Input: Programmable for Start/Stop, Forward/Reverse, Jog
Timer operation: Stop after predetermined time frame
Communications: RS-485 Modbus RTU, Metasys N2, and Apogee FLN P1
USB Port for programming drive with optional PC Software

Frequency Reference Signal

N/A Left or Right Arrow buttons on keypad in Manual Mode
Speed Potentiometer: 0 to +10 Vdc, 10 to 0 Vdc
0-10 Vdc analog input
0/4-20 ma analog input

References

N/A Up to 3 Input References can be selected from Analog
Input #1 or #2, Frequency Input #1 or #2, Network, or Potentiometer

Digital Input Signal

N/A No Operation
Reset after drive trip or alarm
Drive at stop with no holding current
Quick Stop according to Quick Stop Decel Time 1
Stop on input going low
Start
Maintained Start after signal applied for Minimum of 2 ms
Reversing
Start Reverse
Enable Start Forward only
Enable Start Reverse only
Jog
Multi-Step Frequency selection (1 to 8 Steps)
Hold Drive Frequency
Hold Reference
Speed Up; activated by Hold Drive Frequency or Hold Reference
Slow Down; activated by Hold Drive Frequency or Hold Reference
Drive Parameter Setup Select 1-4
Precise Start or Stop; Activated when drive parameter precise start or stop function is selected
Catch Up or Slow Down; Activated by signal to add to or subtract from input reference to control speed
Pulse Input selectable from 100-110000 Hz
Accel / Decel Time select. Set Input to Accel / Decel Times 1 to 4
Digital Potentiometer Input Increase or Decrease
Mechanical Brake Feedback

Keypad

Keypad Features

N/A LCD Display with 6 Alpha-numeric lines. Multi-Language Support
Hot Pluggable, Remote Mount Option, and CopyCat Feature, IP65 rating when remote mounted on enclosure
LED's - Green - drive is on, Yellow - indicates a warning, Red - indicates an alarm, Amber - Indicates active Menu keys and H-O-A keys

Keypad Keys

N/A Status - shows status of drive
Quick Menu - Enters Quick Start, Parameter Data Check, or Trending Modes
Main Menu - Used for programming all drive parameters
Alarm Log - Used to display Alarm list
Back - Reverts to previous step or layer in parameter structure
Cancel - Used to cancel last change or command
Info - Displays information about a command, parameter, or function in any display.
Hand/Off/Auto - Used to control drive locally or put drive in remote mode
Reset - Used to reset Warnings or Alarms

Password

N/A 2 Level Password Protection

Alternate Motor Parameters

N/A Up to 4 Separate complete parameter set-ups are available

Graphical Trending

N/A Trend - Speed, Power, or Frequency

RS485 Modbus RTU Serial Communications

Physical Level

N/A EIA/RS485

Transmission Distance

N/A 1640 ft500 m

Node Address

N/A 32

Transmission Speed

N/A 2400 bits/s4800 bits/s9600 bits/s19200 bits/s38400 bits/s115200 bits/s

Transmission Mode

N/A Half Duplex

Transmission Protocol

N/A Modbus RTU

Character Code

N/A Binary

Character Length

N/A 8 bits

Error Check

N/A CRC

Mounting Clearance

N/A All AF-650 GP drives can be mounted Side-by-Side without spacing. For all drives rated 125 HP or below allow 3.4 inches (100 mm) free space above and below. For all drives rated 150 HP and above allow 8.9 inches (225 mm) free space above and below.

  • 1 24 hour average max of 45 ºC