Item # 6KFP53007X9XXXA1, AF-600 FP Fan and Pump Drives - 575V, 3-Phase, 50/60 Hz Input

List Price $1,610.00

7.5 HP, 575 V




Specifications  · Environmental Conditions  · Standards  · Input Power Supply  · Output  · Control  · Logic Controller (LC) Sequencer  · Process Controller (PID)  · Operation  · Keypad  · RS485 Modbus RTU Serial Communications  · Mounting Clearance

Specifications

Voltage

575 V

Phase

Three

Frequency

50/60 Hz

HP Rating

7.5

kW Rating

5.5

Rated Output Amps

9

Overload Amps (110% 1 Min)

9.9

Standard Unit Includes

IP20 (9) Chassis Keypad

Factory Installed Keypad

Keypad

Drive Type

IP20/Open

A1/B RFI Filter

No A1/B RFI Filter Installed

Load Share

Standard Unit

Conformal Coating

No Conformal Coatings

Revision

1st Revision

Option Kits

NEMA1ACA3, Field Installed IP21/NEMA 1 Add-On Option Kits for AF-650 GP General Purpose Drive ($115.00)

Options and Accessories

OPC24VPS, 24V DC External Supply Module ($240.00)
OPC4XPED, Pedestal Kit ($875.00)
OPCAIO, Analog I/O Module ($500.00)
OPCBAC, BacNet Communications Module ($600.00)
OPCCOVER4142, Power Shield for Unit Size 41 and 42 Drive ($520.00)
OPCCOVER51, Power Shield for Unit Size 51 Drive ($1,305.00)
OPCDEV, DeviceNet Communications Module ($600.00)
OPCEIP, Ethernet IP Communications Module ($700.00)
OPCGPIO, General Purpose I/O Module ($475.00)
OPCLON, LonWorks Communications Module ($600.00)
OPCMBTCP, Modbus TCP Communications Module ($700.00)
OPCPDP, Profibus DP Communications Module ($725.00)
OPCPRT, ProfiNet RT Communications Module ($700.00)
OPCRLY, Relay Output Module ($475.00)
OPCRMKNC, Remote Mounting Kit without cable ($85.00)
OPCTERM, Screw Terminal Accessory ($25.00)
OPCUSB, USB Kit for All Drives up to Unit Size 5X ($75.00)
OPCUSB6X, USB Kit for All Unit Size 6X drive ($225.00)
RMKYPDAC, Remote Mounting Kit for Graphical LCD Keypad ($95.00)


Environmental Conditions

Enclosure

IP00 Chassis
IP20 Chassis

IP21/NEMA 1

IP54/NEMA 12

IP55/NEMA 12

Plenum Ratings

Drives and options are UL rated for installation inside air handling ducts and plenums

Installation Location

Do not install in locations where product could be exposed to dust, corrosive gas, inflammable gas, oil mist, vapor, water drops or direct sunlight. There must be no salt in the atmosphere. Condensation must not be caused by sudden changes in temperature. For use at altitudes of 3280 ft. (1000 M) or less without derating.

Storage Temperature

-25 to 65 ºC

Ambient Temperature1

-10 to +50 ºC

Ambient Humidity

5 to 95 % RH (non-condensing)

Vibration

1.0 g

Cooling Method

Fan Cooled all ratings. Fan Control Auto, 50% level, 75% level, 100% level adjustable
1 24 hour average max of 45 ºC


Standards

Approvals

CE, UL, cUL, and C-Tick
Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes for 208/230 V and 460 V.


Input Power Supply

Rated Input AC Voltage

200-240 Vac, 3-phase, 50-60 Hz, ± 10 % V
380-480 Vac, 3-phase, 50-60 Hz, ± 10 % V

525-600 Vac, 3-phase, 50-60 Hz, ± 10 % V

Max. Voltage Imbalance

3 % of rated supply voltage

True Power Factor

> 0.9 nominal at rated load

Displacement Power Factor

> 0.98

Switching on Input Power Supply

Maximum twice/minute up to 10 HP, Maximum once/minute above 10 HP

Environment According to EN60664-1

Overvoltage category III/pollution degree 2

DC Link Reactors

Built-In DC Link Reactors on all ratings

RFI Filters

Built-In RFI Filters to reduce noise generated by the drive. Meets industrial standards.


Output

Rated Output Voltage

0-100 % of supply voltage

Output Frequency

0-1000 Hz; 0-800 Hz for 460 V above 125 HP and 525-690 V above 125 HP

Switching on Output

Unlimited

Accel/Decel Times

1 to 3600 s

Control Method

Sinusoidal PWM Control (V/Hz, Avd. Vector Control)


Control

Starting Torque

110 % starting torque for 1 minute (variable torque)

Carrier Frequency (Motor Noise)

1 kHz
1.5
kHz
2
kHz
2.5
kHz
3
kHz
3.5
kHz
4
kHz
5
kHz
6
kHz
7
kHz
8
kHz
10
kHz
12
kHz
14
kHz
16
kHz

Torque Boost

0-300 % setting to compensate voltage in relation to the load at low speed

Acceleration/Deceleration Time

0.01-3600 seconds (4 acceleration and deceleration times are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or S-curve)

Data Protection

Password Protection for Quick Menu or Main Menu, 0-9999.

Pattern Operation

Settings via Built-In Logic Controller Sequencer

Jump Frequency Control

4 jump (or skip) frequencies via parameter set to avoid mechanical vibration

Slip Compensation

Maintains motor at constant speed with load fluctuations

Torque Limit Control

Output torque can be controlled within a range of 0.0 to 110 % (0.1 and steps)

8 Preset Speeds

8 programmable preset speeds selectable by 3 digital inputs

Preset Speeds

8 presets via digital inputs

Built-In Communications

Drive RS-485, Modbus RTU, Metasys N2, or Apogee FLN P1

Trim Reference Setting

Available for speed reference offset via potentiometer, voltage input, or current input

DC Injection Braking

Starting frequency: 0.0-1000 Hz, 0-800 Hz for 460 V above 125 HP and 525-690 V above 125 HP
Braking time: 0.0-60.0 seconds
Braking level: 0-100 % of rated current

Jogging Operation

Operation via On key or digital input (Fwd or Rev)

Auto-Restart After Power Failure

Restarts the drive without stopping after instantaneous power failure

Energy Savings

Controls output voltage to minimize motor loss during constant speed operation

Start Mode Function

This functionality smoothly catches a spinning motor

Fire Override Mode

Overrides drive's protective features and keeps motor running

Pump Cascade Controller

Distributes running hours evenly over up to 4 pumps

Sleep Mode

Drive detects low or no flow conditions and adjusts output

Dry Pump Detection

Detects pump operation and can set off alarm, shuts off, or other programmed actions

Belt Monitoring

Drive can detect relationship between current and speed to recognize a broken belt

Real Time Clock

With programmable timed actions


Logic Controller (LC) Sequencer

Logic Controller Events

Up to 38 Programmable Events

Comparators

Array of 6 Comparators

Timers

Array of 8 Timers, adjustable from 0.0 to 3600 sec

Logic Rules

Array of 6 Boolean Logic Rules

Logic Controller States

Array of 20 Logic Controller Action States


Process Controller (PID)

Process PID Controller

4 Auto Tune PID Controllers Built-In

Process CL Feedback Select1

Encoder Option Module
Motor Feedback

No function

Resolver Option Module

Separate Encoder

Process PID Control

Inverse
Normal

Process PID Anti Windup

Disabled
Enabled

Process PID Start Speed

0.0 to 200 Hz

Process PID Proportional Gain

0.00 to 10.00

Process PID Integral Time

0.1 to 10000.0 ms

Process PID Differential Time

0.0 to 10 s

Process PID Differential Gain

1.0 to 50.00

Process PID Feed Forward Factor

0 to 500 %

On Reference Bandwidth

0 to 200 %
1 Up to 2 references.


Operation

Operation Method

Keypad operation: Hand, Off, Auto
Digital Input: Programmable for Start/Stop, Forward/Reverse, Jog
Timer operation: Stop after predetermined time frame
Communications: RS-485 Modbus RTU, Metasys N2, and Apogee FLN P1
USB Port for programming drive with optional PC Software

Frequency Reference Signal

Left or Right Arrow buttons on keypad in Manual Mode
Speed Potentiometer: 0 to +10 Vdc, 10 to 0 Vdc
0-10 Vdc analog input
0/4-20 ma analog input

References

Up to 3 Input References can be selected from Analog
Input #1 or #2, Frequency Input #1 or #2, Network, or Potentiometer

Digital Input Signal

No Operation
Reset after drive trip or alarm
Drive at stop with no holding current
Quick Stop according to Quick Stop Decel Time 1
Stop on input going low
Start
Maintained Start after signal applied for Minimum of 2 ms
Reversing
Start Reverse
Enable Start Forward only
Enable Start Reverse only
Jog
Multi-Step Frequency selection (1 to 8 Steps)
Hold Drive Frequency
Hold Reference
Speed Up; activated by Hold Drive Frequency or Hold Reference
Slow Down; activated by Hold Drive Frequency or Hold Reference
Drive Parameter Setup Select 1-4
Precise Start or Stop; Activated when drive parameter precise start or stop function is selected
Catch Up or Slow Down; Activated by signal to add to or subtract from input reference to control speed
Pulse Input selectable from 100-110000 Hz
Accel / Decel Time select. Set Input to Accel / Decel Times 1 to 4
Digital Potentiometer Input Increase or Decrease
Mechanical Brake Feedback


Keypad

Keypad Features

LCD Display with 6 Alpha-numeric lines. Multi-Language Support
Hot Pluggable, Remote Mount Option, and CopyCat Feature, IP65 rating when remote mounted on enclosure
LED's - Green - drive is on, Yellow - indicates a warning, Red - indicates an alarm, Amber - Indicates active Menu keys and H-O-A keys

Keypad Keys

Status - shows status of drive
Quick Menu - Enters Quick Start, Parameter Data Check, or Trending Modes
Main Menu - Used for programming all drive parameters
Alarm Log - Used to display Alarm list
Back - Reverts to previous step or layer in parameter structure
Cancel - Used to cancel last change or command
Info - Displays information about a command, parameter, or function in any display.
Hand/Off/Auto - Used to control drive locally or put drive in remote mode
Reset - Used to reset Warnings or Alarms

Password

2 Level Password Protection

Alternate Motor Parameters

Up to 4 Separate complete parameter set-ups are available

Graphical Trending

Trend - Speed, Power, or Frequency


RS485 Modbus RTU Serial Communications

Physical Level

EIA/RS485

Transmission Distance

1640 ft
500
m

Node Address

32

Transmission Speed

2400 bits/s
4800
bits/s
9600
bits/s
19200
bits/s
38400
bits/s
115200
bits/s

Transmission Mode

Half Duplex

Transmission Protocol

Modbus RTU

Character Code

Binary

Character Length

8 bits

Error Check

CRC


Mounting Clearance
All AF-650 GP drives can be mounted Side-by-Side without spacing. For all drives rated 125 HP or below allow 3.4 inches (100 mm) free space above and below. For all drives rated 150 HP and above allow 8.9 inches (225 mm) free space above and below.