30 HP, 3600 RPM, NEMA Frame 286TS, 230/460 V, TEFC
    GE Motors has been manufacturing premium efficient motors since the late 1970’s. The latest Energy $aver® design meets EIS Act (Energy Independence & Security Act 2007) efficiency levels (which are based on NEMA Premium® MG1 table 12-12). Other standards and certifications include CSA-Motors and C-390, UL Component & Insulation System Recognition and CE mark for 320 frame and below.
Unit of Measure

Specifications

Enclosure Type

N/A Totally Enclosed Fan Cooled

HP

N/A 30

RPM

N/A 3600

Voltage

N/A 230 V460 V

FLA

N/A 34.5 69.0

Nom. Eff.

N/A 91.7

Frame

N/A 286TS

Price Symbol

N/A G4-7S$P

C Dimension

N/A 27.03 in

Weight

N/A 465 lbs

Norm. Stk.

N/A No

Certification

N/A
EIS Act 2007 Compliant

GEGARD 1800™

NEMA Premium

Manufacturer

N/A
GE

Standard Features

Poles

N/A 2 4

Efficiency

N/A NEMA Premium

Frequency

N/A 50 Hz

NEMA Design

N/A B

Agency Approvals

N/A C-390 - CE mark CSA - Motors UL - Component and Insulation System Recognition

Altitude

N/A 3300 ft

Ambient Temperature

N/A 40 ºC

Balance/Vibration

N/A 0.15 in/sec max

Bearing Type

N/A Ball, Sealed

Conduit Box

N/A Cast Iron

End Shield

N/A Cast Iron

Fasteners

N/A Metric

Frame Material

N/A Cast Iron

Grease

N/A Lithium

Ground

N/A Brass Bolt in Conduit Box

Insulation Class

N/A Class F

Insulation System

N/A GEGARD1800™, Non-Hygroscopic, Anti-Fungus, meets, NEMA MG1-31

Inverter Capabilities

N/A Variable Torque 10:1, Constant Torque 4:1

L10 Bearing Life

N/A Direct Coupled: 65000 hrs, Belted: 26280 hrs

Lifting Means

N/A Eye Bolt

Mounting

N/A F1 as Standard and Modifiable to F2

Mounting Holes

N/A 1 per foot

Nameplate

N/A Stainless Steel

Paint

N/A Buff, Alkyd

Relubrication

N/A No

Rotor

N/A Cast Aluminum

Service Factor

N/A 1.15
Temperature Rise1 N/A 80 ºC

Tests

N/A NEMA Routine, IEEE 112-B

Time Rating

N/A Continuous

Vibration

N/A 0.08 in/s

Warranty

N/A 36 months from date of purchase, 42 months from date of shipment, whichever occurs first

Features

N/A

  • Usable on 200 Volts, 60 Hz, same HP, at 1.0 service factor
  • Usable on 200/400 V, 50 Hz, same HP, at 1.0 service factor
  • Y-Start/Delta-Run Capable
  • Usable on 200/400 V, 50 Hz at 1.15 SF and de-rated to next lower HP

Industries

N/A

  • Oil & Gas
  • Power & Energy
  • Water/Wastewater
  • Cement
  • Pulp & Paper
  • Metals
  • Mining
  • Chemical

Features & Benefits

N/A

  • GEGARD1800™ Insulation System
    The GEGARD1800 insulation system exceeds NEMA MG1-31 standards for motors operating on Inverter power at 460 or 575 volts. Other inverter capabilities include a 10:1 variable torque speed range along with a 4:1 constant torque.
  • Energy Savings
    The Energy $aver TEFC meets US Government EIS Act efficiency levels and also meets NEMA Premium efficiency levels. This motor design has been tested per IEEE 112 Method B to ensure those efficiencies are met. Because of this, energy savings vs. a Pre-EPACT or EPACT motor are significant. For instance, a 100 HP PreEPACT 4 Pole TEFC motor operating 8760 hrs/yr at a rate of $0.06/kWH replaced with a similar Energy $aver TEFC-SD will save you over $1800 every year in energy costs!
  • Severe Duty
    The Energy $aver frame, end shields, fan cover and conduit box are a rugged cast iron construction. It includes a recessed steel reinforced neoprene sling to minimize contaminants from entering the bearing cavity. Additional HP is available at 1.15 service factor for severe applications. A non-hygroscopic, anti-fungus Class F insulation is included, with an 80°C (NEMA B) temperature rise. A 0.08 in/sec vibration meets the IEEE 841 Standard and Y-Start/Delta Runs are designed for 210-320 motor frames.
  • 60/50 Hz Operation
    • 320 Frame and below - 200/400 V @ 50 Hz
    • 286 Frame and below - 200 V @ 60 Hz

  • 1 At 1.0 SF