Matrix Series D Harmonic Filters
Capacitors, Arrestors and Harmonic Filters
Matrix Harmonic filters provide broadband reduction of harmonics. Matrix Harmonic Filters not only offer better performance over other broad band filtering and 18-pulse harmonic reduction techniques, they are also suitable for a wider range of applications. Matrix Harmonic Filters can be installed in either variable or constant torque drive applications and can be applied on either diode or SCR rectifiers. For any application other than variable torque applications, it is suggested that you contact the factory for filter selection.
Product Specifications
-Input Voltage 480 Volts ± 10 %
-Ambient Temperature:
-UL approved - File E191686 for U.S. and Canada
Minimum System Requirements to Achieve Performance Levels
Matrix D Filter performs better than 18-pulse in normal operating conditions.
Selection Table - Matrix D, 480 VAC, 60 Hz, Three Phase, Variable Torque
Applications
Select Matrix filters based on the horsepower (or kilowatt) rating for the adjustable speed drive or the combined current rating of all motors to be connected to the load side of the filter. For variable torque, DC drive or other applications consult factory for proper filter selection.
Source Impedance
If the source impedance is less than 1.5 % impedance, it is required that an input reactor of at least 1.5 % impedance be added in order to have guaranteed performance level. For best value and performance it is recommended that a 3 % line reactor be used whenever the source impedance is less than 1.5 %.
Product Specifications
-Input Voltage 480 Volts ± 10 %
-Ambient Temperature:
- -Storage - 40 ºC to 90 ºC
-Operating - 40 ºC to 50 ºC
-UL approved - File E191686 for U.S. and Canada
Minimum System Requirements to Achieve Performance Levels
- -Source Impedance: 1.5 % minimum to 5 % maximum
-System voltage: 480 Volts (line to line) ± 10 %
-Frequency: 60 Hz ± 0.75 Hz
-Balanced Line Voltage: within 1 %
-Background Voltage Distortion: 0 % THVD
Matrix D Filter performs better than 18-pulse in normal operating conditions.
Selection Table - Matrix D, 480 VAC, 60 Hz, Three Phase, Variable Torque
Applications
Select Matrix filters based on the horsepower (or kilowatt) rating for the adjustable speed drive or the combined current rating of all motors to be connected to the load side of the filter. For variable torque, DC drive or other applications consult factory for proper filter selection.
Source Impedance
If the source impedance is less than 1.5 % impedance, it is required that an input reactor of at least 1.5 % impedance be added in order to have guaranteed performance level. For best value and performance it is recommended that a 3 % line reactor be used whenever the source impedance is less than 1.5 %.
Unit of Measure
Items |
/ImgCustom/1001/placeholder_notavailable.gif 37GMDG0006D Matrix Series D Harmonic Filters List Price $1,623.00
|
/ImgCustom/1001/placeholder_notavailable.gif 37GMDG0008D Matrix Series D Harmonic Filters List Price $1,661.00
|
/ImgCustom/1001/placeholder_notavailable.gif 37GMDG0011D Matrix Series D Harmonic Filters List Price $1,790.00
|
/ImgCustom/1001/placeholder_notavailable.gif 37GMDG0014D Matrix Series D Harmonic Filters List Price $1,821.00
|
/ImgCustom/1001/placeholder_notavailable.gif 37GMDG0021D Matrix Series D Harmonic Filters List Price $2,118.00
|
|||||
Voltage (AC) | N/A 480 V | |||||||||
Phase | N/A Three | |||||||||
Frequency | N/A 60 Hz | |||||||||
Enclosure Type | N/A NEMA 1 & NEMA 2 Drip Proof | |||||||||
Amps | N/A 6 | N/A 8 | N/A 11 | N/A 14 | N/A 21 | |||||
HP | N/A 3 | N/A 5 | N/A 7.5 | N/A 10 | N/A 15 | |||||
Enclosure | N/A CAB-12C2 | |||||||||
HMR Height | N/A | |||||||||
HMR Width | N/A | |||||||||
HMR Depth | N/A | |||||||||
Capacitor Assemblies Height | N/A | |||||||||
Capacitor Assemblies Width | N/A | |||||||||
Capacitor Assemblies Depth | N/A | |||||||||
Storage Ambient Temperature | N/A 40 to 90 ºC | |||||||||
Operating Ambient Temperature | N/A 40 to 50 ºC | |||||||||
Figure | N/A Figure 1 | |||||||||
Weight | N/A 76 lbs | N/A 79 lbs | N/A 83 lbs | N/A 89 lbs | N/A 100 lbs | |||||
Typical Applications |
N/A
Use Matrix Harmonic filters to minimize harmonic current distortion in these and other 6-pulse rectifier applications:
-Water Treatment Facilities -HVAC Systems -AC or DC Motor Drives -Rectifier type welders -Induction Heating Equipment -UPS Equipment -Elevators Matrix Harmonic Filters are multi-stage low pass filters specially configured to avoid the attraction of harmonics from other sources on a shared power system. Matrix filters will not cause power system resonance. However, the configuration of the filter requires that only drives or equivalent loads be loaded on the output of a Matrix harmonic filter. One filter can be used with multiple drives. However, if there is a drive bypass circuit, there must be one filter per drive and the filter and drive combination must be bypassed. Matrix Harmonic Filters are available in a NEMA 1, NEMA 3R or as a modular design preassembled onto panels for subsequent assembly into customer supplied cabinet. |
|||||||||
|