1/2 HP, 460 V

230 Vac, 3-Phase Output
Unit of Measure

Specifications

Voltage (AC)

N/A 460 V

Phase

N/A Three

Input Frequency

N/A 50/60 Hz

HP

N/A 1/2

kW

N/A 0.37

Amps

N/A 1.2
Efficiency1 N/A 95.5
Watt Loss2 N/A 25.5

Height

N/A 6.13 in

Width

N/A 2.76 in

Depth

N/A 6.06 in

NEMA 1 Kit

N/A NEMA1LP1

Din Rail Mounting Kit

N/A RMACLP1

Unit Size

N/A M1

Weight

N/A 2.43 lbs

Accessories

N/A , De-Coupling Plate Kit for 2 HP at 230 V/3 HP at 460 V and Below Drives ($15.00)
, De-Coupling Plate Kit for 3 HP at 230 V/5 HP at 460 V and Below Drives ($15.00)
, De-Coupling Plate Kit for 15 HP at 460 V and Above Drives ($20.00)
, Replacement AF-60 LP Keypad with Potentiometer ($60.00)
, NEMA 1 Kit for 1 HP and Below Drives ($30.00)
, NEMA 1 Kit for 2 HP at 230 V/3 HP at 460 V and Below Drives ($35.00)
, NEMA 1 Kit for 3 HP at 230V/5 HP at 460 V and Below Drives ($40.00)
, NEMA 1 Kit for 15 HP and 20 HP at 460 V Drives ($45.00)
, NEMA 1 Kit for 25 HP and 30 HP at 460 V Drives ($50.00)
, DIN Rail Mounting Kit for 1 HP and Below Drives ($20.00)
, Remote Mounting Kit for Keypad ($25.00)

Factory Installed Keypad

N/A Keypad

Enclosure Type

N/A IP20/Open

Revision

N/A 1st Revision

Environmental Conditions

Enclosure

N/A IP20 (NEMA 1 with optional NEMA 1 kit)

Installation Location

N/A Do not install in locations where product could be exposed to dust, corrosive gas, inflammable gas, oil mist, vapor, water drops or direct sunlight. There must be no salt in the atmosphere. Condensation must not be caused by sudden changes in temperature. For use at altitudes of 3280 ft. (1000M) or less without derating.

Ambient Temperature

N/A -10 to +50 ºC

Ambient Humidity

N/A 5 to 95 % RH (non-condensing)

Vibration

N/A 1.0 g

Storage Temperature

N/A -25 to 65 ºC

Standards

Approvals

N/A CE, UL, cUL, and C-Tick
Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes for 230 V and 460 V.
WEEE and RoHS Compliant

Input Power Supply

Rated Input AC Voltage

N/A 200-240 Vac, 1-phase, 50-60 Hz, ± 10 % V 200-240 Vac, 3-phase, 50-60 Hz, ± 10 % V 380-480 Vac, 3-phase, 50-60 Hz, ± 10 % V

Max. Voltage Imbalance

N/A 3 % of rated supply voltage

True Power Factor

N/A > 0.4 nominal at rated load

Displacement Power Factor

N/A > 0.98

Switching on Input Power Supply

N/A Maximum twice/minute

Environment According to EN60664-1

N/A Overvoltage category III/pollution degree 2

Output

Rated Output Voltage

N/A 0-100 % of supply voltage

Output Frequency

N/A 0-200 Hz (Adv. Vector Control Plus Mode) 0-400 Hz (Volts/Hertz Mode)

Switching on Output

N/A Unlimited

Accel/Decel Times

N/A 0.05 to 3600 s

Overload Current Rating

N/A 150 % of drive rated current for 1 minute

Control

Control Method

N/A Sinusoidal PWM Control (V/Hz with torque vector control)

Switching Frequency Select

N/A 2 kHz4 kHz8 kHz12 kHz16 kHz

Operation Method

N/A Keypad operation: Hand, Off, Auto
Digital Input: Programmable for Start/Stop, Forward/Reverse, Jog
Timer operation: Stop after predetermined time frame
Link operation: RS-485 Modbus RTU

Frequency Reference Setting

N/A Up or Down buttons on keypad or external reference

Analog Input

N/A Built in Potentiometer
0-10 Vdc analog input
4-20 ma analog input

Preset Speeds

N/A 8 presets via digital inputs

Link Operation

N/A Drive RS-485 or Modbus RTU

Second Reference Setting

N/A Switch from speed reference 1 to reference 2 via digital input

Trim Reference Setting

N/A Available for speed reference offset via potentiometer, voltage input, or current input

Acceleration/Deceleration Time

N/A 0.05-3600 seconds (two acceleration and deceleration rates are selectable via digital inputs.
Acceleration and deceleration patterns can be selected from linear or S-curve

DC Injection Braking

N/A Starting frequency: 0.0 to 400 Hz
Braking time: 0.0 to 60.0 seconds
Braking level: 0-150 % of rated current

Frequency Limit

N/A 0 to 400 Hz

Jump Frequency Control

N/A 2 jump (or skip) frequencies via parameter set to avoid mechanical vibration

Jogging Operation

N/A Operation via On key or digital input (Fwd or Rev)

Auto-Restart After Power Failure

N/A Restarts the drive without stopping after instantaneous power failure

Slip Compensation

N/A Maintains motor at constant speed with load fluctuations

Energy Savings

N/A Controls output voltage to minimize motor loss during constant speed operation

Start Mode Function

N/A This functionality smoothly catches a spinning motor

Logic Controller (LC)

Logic Controller Events

N/A Over 23 types of Programmable Events

Comparators

N/A Array of 4 Comparators

Timers

N/A Array of 3 Timers, adjustable from 0.0 to 3600 sec

Logic Rules

N/A Array of 4 Boolean Logic Rules

Logic Controller States

N/A Array of 20 Logic Controller Action States

Process Controller (PI)

Process CL Feedback Select

N/A Analog input 1 Analog input 2 Local bus reference No function Pulse input

Process PI Control

N/A Inverse Normal

Process PI Anti Windup

N/A Disabled Enabled

Process PI Start Speed

N/A 0.0 to 200 Hz

Process PI Proportional Gain

N/A 0.00 to 10.00

Process PI Integral Gain

N/A 0.10 to 9999 s

Process PI Feed Forward Factor

N/A 0 to 400 %

On Reference Bandwidth

N/A 0 to 200 %

Indication

LEDs

N/A Green - drive is on Red - indicates an alarm Yellow - indicates a warning
  • 1 At rated load conditions
  • 2 At rated load conditions