COMPANY HEADER
Print Back
75 HP, 1800 RPM, NEMA Frame 365TP, 460 V, TEFC
Applications:
For use on turbine, mix flow and propeller pumps.

Unit of Measure

Specifications

Usage

N/A Vertical Pump

Enclosure Type

N/A Totally Enclosed Fan Cooled

Phase

N/A Three

HP

N/A 75

RPM

N/A 1800

Voltage

N/A 460 V

Full Load Effi.

N/A 92.4

Frame

N/A 365TP

Disc. Sym.

N/A DS-7VS

Down Thrust

N/A 5600 lbs

Base Dia.

N/A 16 1/2 in

Cplg. Ht.

N/A 30 in

Cplg. BX

N/A 1 1/4 in

Service Factor

N/A 1/4

Ship Wt.

N/A 925 lbs

NEMA Service Factor

N/A 1.15

Type

N/A TU

Features

N/A
  • Class F Insulation, Class B Rise at Full Load (Sine Wave Power)
  • 1.15 Service Factor (Sine Wave Power)
  • Maximum 40ºC. Ambient, 3300 Feet Altitude
  • 230/460 Volt Motors Suitable for 230 Volt Part Winding Start
  • 30 HP & Below Can Be Rerated For 208/415 Volt
  • 50 Hertz Operation at 1.0 Service Factor
  • Inverter Duty Per NEMA MG-1 Part 31 At 1.0 Service Factor
  • Corrosion Resistant Mill & Chemical Duty Paint
  • Stainless Steel Nameplate
  • NRR = Non-Reverse Ratchet, SRC = Self-Release Coupling
  • Discount Symbol 7VS

Manufacturer

N/A
Emerson/US Motors