1/3 HP, 3450 RPM, NEMA Frame 56C, 115/208/230 V
  • Single Phase
  • C Face less Base
  • Division I, Division II, Class I, Groups C & D-Class II, Groups F & G w/Conduit Box

    Explosion-proof for hazardous locations
    Underwriters Laboratories and Canadian Standards Association Listed
    General Specifications:
    These explosion-proof motors are designed and approved for application in hazardous environments having certain explosive gases or materials present.

    Application Notes:
    These motors must be applied in
  • more
Unit of Measure

Specifications

Base

C Face Less Base

Enclosure Type

Totally Enclosed Non-Ventilated

Phase

Single

HP

1/3

RPM 60 Hz

3450

Voltage

115 V208 V230 V

Overload Protection

Automatic

FL Amps 230 V

2.2

% FL Eff.

65.0

NEMA Frame

56C

Disc. Sym.

A

C Dimension

12.88 in

Approx. Weight

38 lbs

Manufacturer


Leeson

Features

N/A

  • These motors are totally enclosed, non-ventilated.

Technical Details

N/A

    No LEESON motors are listed for Class I, Group A or B.
    Class I
    Group A: Acetylene
    Group B: Butadiene, ethylene oxide, hydrogen, propylene oxide, manufactured gases containing more than 30% hydrogen by volume.
    Group C: Acetaldehyde, cyclopropane, diethyl ether, ethylene.
    Group D: Acetone, acrylonitrile, ammonia, benzene, butane, ethanol, ethylene dichloride, gasoline, hexane, isoprene, methane (natural gas), methanol, naphtha, propane, propylene, styrene, toluene, vinyl acetate, vinyl chloride, xylene.

    Class II
    Group E: Aluminum, magnesium and other metal dusts with similar characteristics.
    Group F: Carbon black, coke or coal dust.
    Group G: Flour, starch or grain dust.